cable
CABLE DIAGNOSTIC UNIT:
PD MAPPING
function: scanning and tracing medium voltage(33 and 11 kv) underground cable
tester: Partial Discharge mapping (PD mapping)
IR TESTING IR = insulation resistive
PD MAPPING
function: scanning and tracing medium voltage(33 and 11 kv) underground cable
tester: Partial Discharge mapping (PD mapping)
IR TESTING IR = insulation resistive
Thursday, April 22, 2010
genting sunyen dengkil
Wednesday, April 21, 2010
ULTRA TEV
this handy device have 2 function:
1.ultra sound
2.TEV( transient earth voltage)
ultrasound inspection made for checking circuit breakers compartment condition.
ultrasound checking more to surface inspection.
type of sound produced when a compartment had a problem :
1.corona
2.arking
3.tracking
reading:
0 - -ve dB : ok
1 - +ve dB : not ok
TEV inspection is more to secondary part (relay, thermometer)
TEV reading:
1 - 6 v : internal dischage
7 - 29 v : surface discharge
30v and above : floating metal
primary part: busbar, cable, poteintial transformer and current tranformer
1.ultra sound
2.TEV( transient earth voltage)
ultrasound inspection made for checking circuit breakers compartment condition.
ultrasound checking more to surface inspection.
type of sound produced when a compartment had a problem :
1.corona
2.arking
3.tracking
reading:
0 - -ve dB : ok
1 - +ve dB : not ok
TEV inspection is more to secondary part (relay, thermometer)
TEV reading:
1 - 6 v : internal dischage
7 - 29 v : surface discharge
30v and above : floating metal
primary part: busbar, cable, poteintial transformer and current tranformer
Tuesday, April 20, 2010
VISIT PPU MUTIARA RINI DAMANSARA
type of breaker:
11 kv : AIS (air insulated switchgear)
33kv : GIS (gas insulated switchgear)
JOB:
servicing breakers:
1. cleaning breaker's surface with cotton.
2. spray breaker gear with WD40
3. testing breaker with manually tripping.
11kv breakers serviced done by TNB
33kv breakers serviced done by manufacturer ABB
11 kv : AIS (air insulated switchgear)
33kv : GIS (gas insulated switchgear)
JOB:
servicing breakers:
1. cleaning breaker's surface with cotton.
2. spray breaker gear with WD40
3. testing breaker with manually tripping.
11kv breakers serviced done by TNB
33kv breakers serviced done by manufacturer ABB